PTC-Resistor-Relay Type MSR220K

Version

Price after log in

Ready to ship today,
Delivery time appr. 1-3 workdays

Article number: T228111
Manufacturer: ZIEHL

Do you have a question?

What are the key features of this PTC resistor relay?
What are the applications of the MSR220K?
How many PTC thermistor circuits can the MSR220K monitor?
What is the operating voltage range of the MSR220K?
What are the available output relay options for the MSR220K?
ask something different

ZIEHL PTC-resistor relays protect motors, transformers, machines and equipment against thermal overload. With ZIEHL PTC Sensors MINIKA ® applied they offer best solutions for nominal response temperatures 60°C…180°C.

ZIEHL PTC-resistor relays are designed for PTC-sensors according to DIN 44081 and DIN 44082. Therefor sensor and relays are exchangeable. PTC-resistor sensors are suitable for the installation into windings of electrical machines, bearings and transformers as well as to monitor the temperature of liquid media, airflow and gases.

Used in conjunction, they provide a effectively and reliable protection in case of

  • blocking rotors, heavy starts, countercurrent operation
  • undervoltage and phase failure
  • increased ambient temperature and hindered cooling

Functional overview

  • 1 PTC-resistor set with up to 6 PTC-sensors (250O), or bimetal contacts in series
  • output relay with 1 or 2 change-over contact (co)
  • operating status display with LED
  • K-Housing, vertical terminal order
  • width 22.7 mm
  • snap mounting on 35 mm standard DIN rail or screw mounting
  • electronic reclosing lock (disconnectable)
  • integrated RESET-button
  • link for external RESET
  • automatic RESET at voltage recovery
  • LEDs for power ON (green) and ALARM (red) in reset-button
  • UL recognized component
  • Option: other supply voltages
 

Accessories

MS-Tester
Normal PTC-resistor relays can be tested by simply disconnecting the sensor. PTC-resistor relays with monitoring of sensor short-circuit and break need more sophisticated test-equipment.With help of the ZIEHL MS-Tester also these relays can be easily tested for correct function. The included cable is designed for the connection of relays type MSF 220 V(U). Also any other PTC-resistor relay can be connected to the MS-Tester.Testdisconnect the PTC-resistor relayconnect the MS-Tester (T/0, T/1 and/or T/3) to the sensor inputsswitch on the relayincrease the resistance with the potentiometer (turn slowly) until the appropriate Alarm switchesreduce the resistance until the relay switches back (or a LED signals, that it is ready to switch back)if necessary, the values of the switching points can be measured at the terminals T/0, T/1, T/2 after disconnecting the relay. Typical values are 3000 O ... 4000 O for tripping and >1500 O for switching back.test break with push-button (only at relays with monitoring of sensor/line-break)test short circuit with push-button (only at relays with monitoring of sensor/lineshort-circuit)ATTENTION: At relay MSF 220 V(U), break or short-circuit in any sensor will result in an error message = ALARM 1. The LED "sensor" lights and the LED of the appropriate alarm blinks.HINT: cold PTCs have a resistance of 20...250 O, typical 50...120 O per sensor.
Questions about PTC-Resistor-Relay Type MSR220K
ProxaChatbaseAI.questions.logo

Zetty

Digital Assistant

ProxaChatbaseAI.questions.logo

Welcome to ZIEHL industrie-elektronik GmbH + Co KG! I am Zetty, your digital assistant. Since many of my answers are generated by artificial intelligence, please double-check important information to make sure everything is correct.

Content partly AI-generated. Before using our products, it is necessary by qualified personnel is required. No liability for incorrect information. Learn more
ProxaChatbaseAI.questions.logo