Universal Measuring Transducer Type MU2000K
Measuring Transducer AC and DC, for Voltage and Current, scaleable
Product description
Measuring transducers MU2000K can measure DC- an AC-voltages up to 600 V and DC- and AC-currents 0-1/5 A.
Preset measuring ranges can be selected. More measuring ranges (zero and full-scale) can be easily scaled. The output signals DC 0/2-10 V and 0/4-20 mA are insulated from measuring input and supply voltage. With its universal supply voltage AC/DC 24-240 V the measuring transducer can be connected to all common supply voltages.
The MU2000K e.g. is suitable for measuring DC voltages and charging currents at batteries or for measuring AC voltages and currents in plants for own generation of energy.
Overview of functions
- Output signal 0-20mA and 0-10V or 4-20mA and 2-10V
- Rated Supply Voltage AC/DC 24-240V
- Insulation between inputs, outputs and supply voltage
Inputs
- AC/DC 0 … 600 V (preset values: 0…30 V / 80…120 V / 0…150 V / 0…300 V / 0…600 V)
- AC/DC 0 … 5 A (preset values: 0…1 A / 0…5 A)
- In measuring ranges for AC also DC-signals can be measured. Negative signals will be measured as positive signals.
Zeros and Full Scales for more measuring-ranges can be freely selected by the user.
Technical Data
Rated supply voltage Us
AC/DC 24V-240 V, 0/50/60 Hz < 3 W < 8 VA
DC 20,4 - 297 V, AC 20 - 264 V
Input voltage
AC/DC 0-30/150/300/600 V, 80-120 V, Ri = 500 kΩ, max. 600 V, max. 300 V to GND
Accuracy
DC ≤ 0,2% AC ≤ 0,5% (50/60 Hz) from full scale, drift < 0,02 %K
Input current
AC/DC 1A, 5A, max. 7,5A/4s, 25A/1s, 30 mΩ
Accuracy
DC ≤ 0,2% AC ≤ 0,5% (50/60 Hz) from full scale, drift < 0,02 %K
Measuring method / Resoulution
RMS (AC), averaging (DC), resolution 14 Bit
Output voltage
DC 0/2-10 V, load min. 1 kΩ
Accuracy
≤ 0,3 % from full scale, drift <0,01 %/K
Resolution
11.6 Bit, <3,1 mV
Output current
DC 0/4-20 mA, load max. 500 Ω
Accuracy
≤ 0,3 % from full scale, drift <0,015 %/K
Resoulution
11,6 Bit, <6,1 mA
Error load
0,3 % of current x (250Ω - load) / 250Ω
Galvanic insulation
Supply voltage - input - output
Measuring time / Averaging
45 ms + 20 ms x number of averages (1/2/8/16/32 values)
Test conditions
Rated ambient temperature range
-20 °C ... +50 °C
Housing dimensions (h x w x d)
design K, 75 x 22,5 x 115 mm
Protection housing/terminals
IP 40 / IP 20
Attachment
DIN rail 35 mm or screws M4
Weight
ca. 100 g
CAD Data
Certificates
FAQ / Product videos