Voltage- and Frequency-Relay type SPI1021

Price after log in

Ready to ship today,
Delivery time appr. 1-3 workdays

Article number: S222300
Manufacturer: ZIEHL

Grid- and Plant Protection According to CEI 0-21 (Italy) and DEWA-standard (Dubai) (DRRG), with integrated Vector-Shift Relay.

The SPI1021 monitors voltage and frequency in plants for own generation of electricity. It fulfills the requirements of CEI 0-21 (Italy) and DEWA-standard (Dubai) Interface Protection (IP) according to DEWA Distributed Rrnewable Resources Generation programme (DRRG19, September 01, 2016).
6 selectable programs allow measuring, 3 phases to neutral (4-wire mode), 3 phases phase-phase (3-wire mode) and single phase to neutral (2-wire). The SPI1021 can monitor all decentralized power plants, photovoltaic, wind or thermal, that feed in the low or medium voltage grid. In applications with possible asymmetry >6kVA, power balance has to be monitored extra.

In programs 1-3 (3=default) the limits are preset according to CEI 0-21 (Italy), in programs 4-6 they are preset according to DEWA-standard (Dubai). They can be changed if required and be protected with a code and/or a seal.

A counter for alarms and standbys stores the last 100 events with reason and elapsed time. In addition the time the SPI1021 has interrupted the plant is recorded. All values can be read displayed at the device and give the operator valuable information about the availability of the plant. The standby input allows a remote shutoff e.g. with a RCR. It can also be used to switch to an energy saving mode by a timer or a twilight switch. Number of standbys and added time are stored and can be read in the display.

Summary of the functions

When the device has been installed, a self-test starts automatically. The self-test can be repeated when required. All values of the test are stored and can be read out at the display.

  • Monitoring of under- and overvoltage 0/15-520 V
  • Measuring of 3 phase with or without neutral or single phase
  • Monitoring of over- and underfrequency 45-65 Hz
  • Monitoring of quality of voltage (10-minutes-average)
  • Monitoring of vector-shift (connectible)
  • Input IN2 for selection of frequency window
  • Input In3 for selection of mode transitory or definitive
  • Input Y0/Y1 for monitoring function of connected switch (automatic detection of nc/no)
  • Relay K2 picks up (on time <500ms) only at failure at switch connected to K1
  • 2 restarts at switch-on error of connected switch
  • Selftest with storing of values
  • Switching delays adjustable 0,05…130 s
  • Switching-back-delays adjustable 0…999 s
  • Different switching time according to type of alarm and selected mode
  • Switch-on delay 300 s
  • All parameters preset according to CEI 0-21
  • Alarm counter for 100 alarms with value, reason and elapsed time
  • Recording of added time of alarms
  • Input for standby (off time <50ms) with counter and recording of time
  • Simulation for testing
  • Sealing, all parameters can be read out while sealed
  • Easy installation and programming with 6 preset programs
  • Supply-voltage AC/DC 24-270 V
  • Housing for DIN-rail-mount, 105 mm wide, mounting height 70 mm


Alternativen

Voltage and Frequency Relay Type UFR1001E
The grid- and plant protection device UFR1001E monitors voltage and frequency in plants for owngeneration of electricity. It complies with the requirements of VDE-AR-N 4120:2018-11, VDE-AR-N 4110:2018-11, VDE-AR-N 4105:2018-11, G98 and G99, ÖVE/ÖNORM E 8001-4-712:2009 and other standards for generators connected to the public grid.The UFR1001E is a dual-channel device and thus one-fault-proof. The function of the output-relays and of the connected switches can be monitored with feed-back contacts. When a connected switch does not switch off, the UFR does not switch on again. When a switch does not switch on it makes 2 restarts and thus improves availability of monitored plant.The limits are pre-set according to VDE-AR-N 4105-2011-08, VDE-AR-N 4105:2018-11 and other standards. They can be changed if required and be protected with a code and/or a seal.With a 2-step test both channels can be tested individually and the triggering time of connected switches is measured.The standby input allows a remote shutoff e.g. with a RCR.NEW: Our UFR1002IPWould you like to measure upt o 1,200 V?You need an interface (Modbus TCP)?You want a plain text LCD display?You need a seperate life contact?Then Take a look at the new UFR1002IP! 
Relay for Voltage and Frequency UFR1002IP
NEW: For the German regulation "NELEV" and "EAAV"The grid decoupling relay UFR1002IP is the "big brother" of the UFR1001E and monitors voltage and frequency in three-phase and AC grids.With a color LCD display (German/English) and joystick, it is even easier to operate than the UFR1001E. Measured values and settings are clearly displayed. The device can be programmed, updates installed and the alarm memory read out via the integrated IP interface. The real-time clock (with power reserve) simplifies the traceability of the alarms. Up to 1,200 V can be monitored in conjunction with the VG1200 coupling device. The device has a two-channel, single-fault-safe design and thus meets the requirements of VDE-AR-N 4105:2018-11. The function of the connected switch is monitored. If monitoring is activated, the device does not switch on again if a switch-off error is detected.Limit values for different applications are preset. Where permitted, they can easily be changed. If the nominal voltage is changed, the device automatically adjusts the limit values. With the standby input, a remote shutdown can be implemented, e.g. with a ripple control receiver.Monitoring ofUnder/over voltage 15-520V (with ZIEHL VG1200 coupling device up to 1,200 V)Under/over frequency 45-65 HzVoltage quality (10-minute average)Vector shift 2-65°ROCOF, rate of change of frequency df/dt 0.100...5.000 Hz/sZero voltage U0 (ANSI 59v0)passive anti islanding protectionFeatures:single-fault-proof, with monitoring of connected switch (can be switched off when using the integrated switch of PV and battery convertersProgrammable restart attempts in the event of a switch-on error in the connected switchRelay K3 with programmable functions, including life contact, delayed switch-on signal for switches or error messagesResponse time adjustable 0.05 … 300,0 sSwitch-back time adjustable 0 … 6,000 sPreset according to VDE-AR-N 4105-2018-11 (Pr 1.02, Pr 1.08 + 1.09) and VDE-AR-N 4105-2011-08 (Pr 1.01)Preset according to VDE-AR-N 4110-2018-11 (Pr 1.11-1.14) and bdew guideline (Pr 1.03-1.06)automatic adjustment of the switching points when the nominal voltage is changedAlarm counter for 100 alarms (with trigger value, cause and date/time, time of restart)3 programmable digital inputsStandby counter and timer with standby on/off date/timeTest and simulation function with measurement of switch-off timesSealing option and code protection for settingsInterface ethernet TCP/IP, values available via modbus TCPSimple commissioning and programming thanks to preset basic programs and transmission via IP interfaceSupply voltage AC/DC 24-270 VHousing for DIN-rail-mount, 105 mm wide, mounting height 66 mmAccessory: Installation frame ER6 for panel mount
Coupling Device for Voltage Type VG1200
In order to achieve higher efficiencies and to reduce line losses, inverters with a higher output voltage than the usual 3AC 400 V are often used in large on-site generation systems.So that the grid and system protection can monitor this high voltage, it must be reduced. This is usually done with voltage converters. With the VG1200 coupling device, an ohmic voltage divider is available that takes on this task. In conjunction with the VG1200 coupling device, the UFR1002IP can measure voltages of up to 1200 V. The display in the UFR1002IP is scalable. This means that the voltages at the input of the VG1200 are displayed and the limits for protection against over- and undervoltage are set accordingly. Both devices together meet the requirements of VDE-AR-N 4110 (feeding into the medium-voltage grid).Measuring of voltage up to 1200 VMeasuring tolerance = 1,2% of nominal voltage (of UFR1002IP)No voltage converters requiredDisplay of the correct voltage on the UFR1002IP (scalable)No supply voltage requiredHousing V6, 105 mm wide 

Passendes Zubehör

Front Mounting Kit Type ER
You found a device in that meets your requirements and you want to install it in a control panel or in the door of a control cabinet?With the installation frame of the ER series, this is possible for all ZIEHL devices in housings V4, V6 and V8 (width 70/105/140 mm).Enclosed by a high-quality frame made of anodized aluminum, all displays can be read outside the control cabinet. Switches, buttons and joystick can be operated.