Voltage- and Frequency-Relay UFR1001

Voltage- and Frequency Relay with integrated Vector-shift Relay, sealable

Voltage- and Frequency-Relay UFR1001

Part number

Product description

 

The voltage- and frequency-relay UFR1001 monitors voltage and frequency in two- or three-phase networks with or without neutral and switches off rapidly when required.

The device can be easily adapted to the requirements of the carrier of the power network. With the integrated vector-step relay it can also monitor networks at synchronous generators. 

After selecting a basic program, for each relay limits can be programmed for over-/undervoltage and over-/underfrequency. In programs with vector-stepmonitoring, K2 is used for vectorstep only.

Applications are monitoring power-networks at great solarplants, in block power heating stations, also with synchronous generators (vector shift) or generally monitoring the quality in power networks at machines or power-supplies.

  • monitoring of over- and undervoltage 40…520 V
  • monitoring of over- and underfrequency 45…65 Hz
  • monitoring of quality of voltage (10-minutes-average)
  • monitoring of vector-shift 2…20 °, 1 or 3-phase
  • Switching-delay adjustable <0,05…60,0 s
  • Switching-back-delay adjustable 0…1000 s
  • Alarm-counter for up to 100 alarms (with measured value and reason)
  • Added time of alarm up to 999 hours. Displays the time, alarms have been active (while supply voltage applied only)
  • LEDs for alarms, allocation of values and states of relays
  • 2 output-relays, each for monitoring frequency and/ or voltage
  • function of relays (nc- or no -operating mode) programmable
  • interlocked switching or autoreset
  • input for Enable / Reset
  • easy programming by help of basic programs
  • Sealing of settings is possible
  • code-lock against manipulation of settings
  • universal power-supply AC/DC 24-270 V
  • housing for DIN-rail-mount, 70 mm wide, mounting height 66 mm

 

Technical Data

Power supply

Rated supply voltage Us

.......

AC/DC 24-270 V, 0/45...65 Hz, <5VA
DC: 20,4...297 V, AC: 20,4...297 V

 

Relay output

.......

2 change-over contacts
type 2, see general technical informations

 

Voltage

Measuring voltage phase - phase

.......

AC 40...520 V

 

Measuring voltage phase - N

.......

AC 40...300 V

 

Hysteresis

.......

adjustable 1...99 V

 

Frequency

.......

45...65 Hz

 

Error (with N)

.......

± 0,8% of measured value ± 1 Digit

 

Error (without N)

.......

± 1% of measured value ± 1 Digit

 

Measuring functions

.......

3-phase with / without neutral, single phase to neutral

 

Switching-delay

.......

adjustable 0,05...60,00 s

 

Switching-back delay (zerovoltage-proof)

.......

adjustable 0 (> 200 ms)...1000 s

 

Frequency

Measuring range

.......

45,00...65,00 Hz

 

Hysteresis

.......

0,05...5,00 Hz

 

Error

.......

± 0,05 Hz ± 1 Digit

 

Switching-delay

.......

adjustable 0,1...99,9 s

 

Switching-back delay

.......

adjustable 0...240 s

 

Vector-Shift

Mathod

.......

1- or 3-phase

 

Measuring range

.......

2,0...20,0 °

 

Hysteresis

.......

0,1 °

 

Switching-delay

.......

< 50 ms

 

Switching-back delay

.......

adjustable 3...240 s

 

Delay at Us on

.......

adjustable 2...20 s

 

Test Conditions (EN 60 255)

Rated impulse voltage

.......

4000 V

 

Overvoltage catagory

.......

III

 

Rated Insulation voltage

.......

AC 300 V

 

Contamination level

.......

2

 

Isolation material group

.......

II

 

On-period

.......

100 %

 

Rated ambient temp. range

.......

-20 °C...+55 °C EN 60 068-2-1 dry heat

 

Interference resistance

.......

EN 61 000-6-2

 

Interference transmission

.......

EN 61 000-6-4

 

Housing

Design

.......

V 4

 

Dimensions (h x w x d)

.......

90 x 70 x 58 mm, mounting height 66 mm

 

Protection housing

.......

IP 30

 

Protection terminals

.......

IP20

 

Attachment

.......

DIN-rail 35 mm or screws M4

 

Weight

.......

app. 200 g